VYF-12GD Indoor Three Position Vacuum Circuit B...
Selection Note: If there is no grounding switch, the grounding operation shaft acts as an interlocking shaft, and the external dimensions remain unchanged. Operating conditions ● Ambient temperature: -25℃ +40℃; ● Relative humidity: daily average <95%, monthly average <90%; ● Altitude: not higher than 1000m; ● Earthquake intensity: no more than 8 degrees: ● Place of use: No explosion hazard, chemical and severe vibration and pollution. ● Service conditions above an altitude of 1000 mete...
ZW20-12 Outdoor Vacuum Circuit Breaker
Selection Operating conditions 1. Altitude≤2000 meters 2. The environment temperature: -30℃ ~+55℃ outdoor; the highest annual average temperature 20 ℃, the highest daily average temperature 30 ℃; 3. Relative humidity: 95% (25℃) 4. Seismic capacity: horizontal ground acceleration 0.3g, vertical ground acceleration 0.15g, at the same time duration of three sine waves, a safety factor of 1.67 5. Earthquake intensity: 7 degrees 6. The maximum daily temperature difference: 25 ℃ 7. The intensity o...
JN22-40.5/31.5 Indoor Grounding Switch
Selection Operating conditions 1. Ambient temperature:-10~+40℃ 2. Altitude: ≤1000m 3. Relative humidity: Day average relative humidity ≤95% Month average relative humidity ≤90% 4. Earthquake intensity: ≤8degree 5. Appliable in the place without corrosive, flammable gas and water place 6. With no frequently intense vibrant place around. Technical data Item Units Data Rated voltage kV 35 Maximum voltage kV 40.5 Rated short time withstand current kA 31.5 Rat...
GW4 Outdoor Isolation Switch
Selection Technical data Item Unit Parameters GW4- 40.5 GW4- 72.5 GW4- 126 GW4- 126G GW4- 145 Rated voltage KV 40.5 72.5 126 126 145 Rated current A 630 1250 2000 2500 630 1250 2000 2500 4000 630 1250 2000 2500 630 1250 1250 2000 2500 Rated short-time withstand current (RMS) KA 20 31.5 40(46) 20 31.5 40(46) 20 31.5 40(46) 20 31.5 20 31.5 40(46) Rated peak withstand current (peak) KA 50 80 100(104) 50 80 100(104) 50 80 100(104) 50 80 50 80 100(104) Rated short-time withstand...
FZN25/FZRN25-12 Indoor Vacuum Load Switch
Selection Operating conditions 1. Ambient air temperature: upper limit +40℃, lower limit -25℃ (allow storage at – 30℃), 24h average value is not higher than +35℃; 2. Altitude: no more than 1000m; 3. Relative humidity: daily average value is not greater than 95%, monthly average is not greater than 90%; 4. Earthquake intensity: do not exceed 8 degree; 5. The surrounding air is not corrosive and flammable gas,steam and other significant pollution; 6. No regular violent vibration; 7. Cont...
ZW7-40.5 Outdoor Vacuum Circuit Breaker
Operating conditions 1. Ambient temperature: upper limit +40℃, lower limit -30℃; Days difference does not exceed 32K; 2. Altitude: 1000m and the following areas; 3. Wind pressure: not more than 700Pa (corresponding to the wind speed 34m/s); 4. Air pollution level: IV class 5. Earthquake intensity: do not exceed 8 degree; 6. Ice thickness: no more than 10mm. Technical data Item Unit Parameter Voltage, current parameters Rated voltage kV 40.5 Rated short time power frequency withstan...