YSM6-12~24 Air-insulated RMU(Fixed Type)
Selection Operating conditions 1. Air temperature: Maximum temperature: +40℃; Minimum temperature:-5℃ 2. Humidity: Monthly average humidity 95%; Daily average humidity 90% . 3. Altitude above sea level: Maximum installation altitude: 2000m 4. Ambient air not apparently polluted by corrosive and flammable gas, vapor etc. 5. No frequent violent shake Features 1. Incoming unit with switch disconnector(Load break switch) schemas With other extra components optional Outg...
GN19-12 Indoor Isolation Switch
Technical data Model Rated voltage (kV) Maximum voltage (kV) Maximum current (A) 4S thermal stability current (kV) Dynamic stability current (kV) GN19-10(C)400-12.5 10 11.5 400 12.5 31.5 GN19-10(C)630-20 10 11.5 630 20 50 GN19-10(C)1000-31.5 10 11.5 1000 31.5 80 GN19-10(C)1250-40 10 11.5 1250 40 100 Overall and mounting dimensions(mm)
JN15-12 Indoor Grounding Switch
Selection Operating conditions 1. Ambient temperature:-10~+40℃ 2. Altitude: ≤1000m (sensor height:140mm) 3. Relative humidity: Day average relative humidity ≤95% Month average relative humidity ≤90% 4. Earthquake intensity: ≤8degree 5. Dirtiness degree: II Technical data Item Units Data Rated voltage kV 12 Rated short time withstand current kA 31.5 Rated short circuit withstand time s 4 Rated short circuit making current kA 80 Rated peak withstand current kA 80 Rated 1min powe...
ZW7-40.5 Outdoor Vacuum Circuit Breaker
Operating conditions 1. Ambient temperature: upper limit +40℃, lower limit -30℃; Days difference does not exceed 32K; 2. Altitude: 1000m and the following areas; 3. Wind pressure: not more than 700Pa (corresponding to the wind speed 34m/s); 4. Air pollution level: IV class 5. Earthquake intensity: do not exceed 8 degree; 6. Ice thickness: no more than 10mm. Technical data Item Unit Parameter Voltage, current parameters Rated voltage kV 40.5 Rated short time power frequency withstan...
YVG-12 Solid Insulation Ring Network Cabinet
Selection Classified by functional units in the system: incoming cabinet, outgoing cabinet, buscouple cabinet, metering cabinet, PT cabinet, lifting cabinet, etc., represented by wiring scheme number. According to the type of main switch components, it is divided into: load switch cabinet, load switch fuse combination electrical cabinet, circuit breaker cabinet, and isolation switch cabinet, etc., represented by F (fuse combination electrical appliance), V (circuit breaker), C (load switch),...
ZN85-40.5 Indoor Vacuum Circuit Breaker
Selection Operating conditions 1. Ambient temperature -10℃ ~ +40℃ 2. Altitude ≤ 1500m; 3. Relative humidity: the daily average is not greater than 95%, the monthly average is not greater than 90%, the daily average of saturated steam is not greater than 2.2*10-³Mpa, and the monthly average is not greater than 1.8*10-³Mpa; 4. The earthquake intensity does not exceed 8 degrees; 5. Places free of fire, explosion hazards, severe pollution, chemical corrosion and severe vibrations. Features 1. Ad...