ZW7-40.5 Outdoor Vacuum Circuit Breaker
Operating conditions 1. Ambient temperature: upper limit +40℃, lower limit -30℃; Days difference does not exceed 32K; 2. Altitude: 1000m and the following areas; 3. Wind pressure: not more than 700Pa (corresponding to the wind speed 34m/s); 4. Air pollution level: IV class 5. Earthquake intensity: do not exceed 8 degree; 6. Ice thickness: no more than 10mm. Technical data Item Unit Parameter Voltage, current parameters Rated voltage kV 40.5 Rated short time power frequency withstan...
XRNT Current-limiting Fuses for Transformer Pro...
Selection Technical data Type Rated voltage Rated current of the fuse (A) Rated current of the fuselink (A) XRNT-12 12 40 3.15、6.3、10、16、20、25、31.5、40 XRNT-12 12 100 50、63、71、80、100、(125) XRNT-12 12 125 125、160、200、250 XRNT-24 24 200 3.15、6.3、10、16、20、25、31.5、40、50、63、80、100、125、160、200 XRNT–40.5 40.5 125 3.15、6.3、10、16、20、25、31.5、40、50、63、80、100、125、160、200 Overall and mounting dimensions(mm) Chat1/a link XRNT-12Kv Chat2/a li...
ZW8-12 Outdoor Vacuum Circuit Breaker
Selection Operating conditions 1. Ambient temperature: upper limit +40℃, lower limit -30℃; 2. Altitude ≤ 2000 meters 3. Pressure: not more than 700Pa (corresponding to the wind speed 34m/s); 4. Earthquake intensity: do not exceed 8 degree; 5. Pollution grade: III class; 6. Maximum daily temperature variety less than 25℃. Technical data Item Unit Parameter Voltage, current parameters Rated voltage kV 12 Rated short time power frequency withstand voltage (1min) kV 42 Rated lightn...
ZN85-40.5 Indoor Vacuum Circuit Breaker
Selection Operating conditions 1. Ambient temperature -10℃ ~ +40℃ 2. Altitude ≤ 1500m; 3. Relative humidity: the daily average is not greater than 95%, the monthly average is not greater than 90%, the daily average of saturated steam is not greater than 2.2*10-³Mpa, and the monthly average is not greater than 1.8*10-³Mpa; 4. The earthquake intensity does not exceed 8 degrees; 5. Places free of fire, explosion hazards, severe pollution, chemical corrosion and severe vibrations. Features 1. Ad...
JN15-24 Indoor Grounding Switch
Selection Operating conditions 1. Ambient temperature:-10~+40℃ 2. Altitude: ≤2000m 3. Relative humidity: Day average relative humidity ≤95% Month average relative humidity ≤90% 4. Earthquake intensity: ≤8degree 5. Class of pollution: II Technical data Item Units Data Rated voltage kV 24 Rated short time withstand current kA 31.5 Rated short circuit withstand time S 4 Rated short circuit making current kA 80 Rated peak withstand current kA 80 Rated 1min power frequency withstan...
ZN63M-12 (Magnetic type) Indoor Vacuum Circuit ...
Selection ZN63M - 12 P M 630 - 25 HT P210 Name Rated voltage(KV) Pole type Operating mechanism Rated current(A) Rated short-circuit breaking current(KA) Installation Phase spacing Indoor vacuum circuit breaker 12:12KV No mark: Insulating cylinder type P Solid -sealing type M: Insulating cylinder type permanent magne 630, 1250, 1600, 2000, 2500, 3150, 4000 20, 25, 31.5, 40 HT: Handcart FT: Fixed type P150, P210, P275 Note: The phase spacing of ZN63-12□M is usually P210mm, whic...