S9-M Series Oil-immersed Fully Sealed
Selection Operating conditions 1. Ambient temperature: maximum temperature: +40°C, minimum temperature: -25℃ . 2. Average temperature of the hottest month:+30℃, average temperature in the hottest year: +20℃ . 3. Altitude not exceeding 1000m. 4. The waveform of the power supply voltage is similar to a sine wave. 5. The three-phase supply voltage should be approximately symmetrical. 6. The total harmonic content of the load current shall not exceed 5% of the rated cur...
ZW32-24 Outdoor Vacuum Circuit Breaker
Selection Operating conditions 1. Ambient air temperature: The daily temperature variation: -40℃ ~+40℃ diurnal variation of temperature less than 25℃; 2. Altitude: no more than 2000 meters 3. Wind speed is no more than 35m/s (equivalent to 700Pa on the surface of the cylindrical); 4. Ice cover thickness no more than 10mm; 5. The intensity of sunshine not more than 1000W/m ² 6. Pollution degree no more than GB 5582 IV class 7. Seismic intensity does not exceed 8 class 8. No flammable, explosi...
ZN23-40.5 Indoor Vacuum Circuit Breaker
Selection Operating conditions 1. The environment temperature: upper limit +40℃, lower limit -15℃ (cold area -25℃); 2. Altitude: not more than 2000m; 3. Relative humidity: daily average value is not greater than 95%, monthly average is not greater than 90%; 4. Saturated steam pressure: daily average value is not higher than 2.2 × 10 -3 Mpa,monthly average is not higher than 1.8×10-3 Mpa; 5. Earthquake intensity does not exceed 8 degrees; 6. No fire, explosion, pollution, chemical corrosion a...
RN1 Indoor Current Limiting Fuse
Features Current which passes the fuse when being1.3 times of itsspecified electric current,Do not fusing for an hour; Whenthe current through the fuse is 2 times of its specinedelectric current,fusing in an hour;Refer to its fusingfeature curve in chart 1when select the fuse. Figure 1 RN1/RN3“An-second” characteristic curve Technical data 3 6 10 35 Rated current (A) 20 100 200 300 400 200 75 100 200 300 20 50 75 100 200 7.5 10 20 30 40 Max breaking curent KV effective vakue 40 1.3...
LZZBJ18 Current Transformer
Selection Technical data 1. Rated insulation level: 10kV:12/42/75kV; 20kV:24/65/125kV 2. Power factor of load: cosΦ=0.8(lagging) 3. Rated secondary current: 5A(or 2A,1A) LZZBJ18-10/150b/2 Type Rated primary current (A) 1s thermal current (kA virtual value) Dynamic standing current (kA peak) Accuracy class combination (1S/2S) Rated secondary output(VA) 0.2S 0.5 5P15 10P15 20 2 5 0.2/0.5/10P10 0.2/0.5/5P10 0.5/0.5/10P10 0.2/0.2/10P10 0.5/0.5/5P10 0.2/0.2/5P10 10 10 15 30 3 7.5 ...
PRW1 Drop-out Fuse
Selection Operating conditions 1. Suitable for environments with an upper limit of 40 ℃ and a lower limit of -30 ℃ . 2. Altitude not exceeding 1000m, wind speed not exceeding 35m/s 3. Fuses are not suitable for the following locations 3.1 Places with fuel or explosion hazards. 3.2 Places with severe vibration or impact. 3.3 Areas with abnormal electrochemical gas effects and severe air pollution and smoke Technical data parameter of porcelain housed fuse Type Rated voltage (kV) Rated curr...