ZW32-24 Outdoor Vacuum Circuit Breaker
Selection Operating conditions 1. Ambient air temperature: The daily temperature variation: -40℃ ~+40℃ diurnal variation of temperature less than 25℃; 2. Altitude: no more than 2000 meters 3. Wind speed is no more than 35m/s (equivalent to 700Pa on the surface of the cylindrical); 4. Ice cover thickness no more than 10mm; 5. The intensity of sunshine not more than 1000W/m ² 6. Pollution degree no more than GB 5582 IV class 7. Seismic intensity does not exceed 8 class 8. No flammable, explosi...
ZN63(VS1)-12 Indoor Vacuum Circuit Breaker (Ins...
Selection ZN63 - 12 T 630 - 25 HT P210 Model Rated voltage(KV) Operating mechanism Rated current(A) Rated short-circuit breaking current(KA) Installation Phase spacing Indoor vacuum circuit breaker 12:12KV T: Spring type 630,1250, 1600,2000, 2500, 3150, 4000 20, 25, 31.5, 40 HT: Handcart FT: Fixed type P150, P210, P275 Note: ZN63-12 adopts a double spring integrated mechanism by default. If a single spring modular mechanism is required, a single spring needs to be added to the mod...
ZW32Y-12 Outdoor Vacuum Circuit Breaker
Selection Operating conditions 1. Ambient temperature: upper limit +40℃, lower limit -30℃; 2. Altitude: ≤2000m; 3. Wind pressure: not more than 700Pa (corresponding to the wind speed 34m/s); 4. Earthquake intensity: do not exceed 8 degree; 5. Pollution grade: III class; 6. Maximum daily temperature variety less than 25℃ . Technical data Item Unit Parameter Rated voltage kV 12 Rated insulation level 1min power frequency withstand voltage Dry test Wet test kV 42/ fracture 48 kV 34 ...
ZN63 (VS1)-12C Vacuum Circuit Breaker (Side-Ope...
Selection ZN63 C - 12 P / T 630 - 25 FT R P210 Name Structure - Rated voltage(KV) Pole type / Operating mechanism Rated current(A) - Rated short-circuit breaking current(KA) Installation Main circuit wiring direction Phase distance Indoor vacuum circuit breaker Side operation - 12:12KV No mark: Insulating cylinder type P: Solid-sealing type / T:Spring type 630 1250 1600 2000 2500 3150 4000 - 20 25 31.5 40 FT: Fixed type L: Left R: Right P210 Note: 1. order a ZN63 si...
FZN25/FZRN25-12 Indoor Vacuum Load Switch
Selection Operating conditions 1. Ambient air temperature: upper limit +40℃, lower limit -25℃ (allow storage at – 30℃), 24h average value is not higher than +35℃; 2. Altitude: no more than 1000m; 3. Relative humidity: daily average value is not greater than 95%, monthly average is not greater than 90%; 4. Earthquake intensity: do not exceed 8 degree; 5. The surrounding air is not corrosive and flammable gas,steam and other significant pollution; 6. No regular violent vibration; 7. Cont...
FLN36 Indoor SF6 Load Switch
Selection Operating conditions 1. Air temperature Maximum temperature: +40℃; Minimum temperature:-35℃. 2. Humidity Monthly average humidity 95%; Daily average humidity 90%. 3. Altitude above sea level Maximum installation altitude: 2500m. 4. Ambient air not apparently polluted by corrosive and flammable gas, vapor etc. 5. No frequent violent shake. Technical data Ratings Unit Value Rated voltage kV 12 24 40.5 Rated lighting impulse withstand voltage kV 75 125 170 Common value Acro...