ZN85-40.5 Indoor Vacuum Circuit Breaker
Selection Operating conditions 1. Ambient temperature -10℃ ~ +40℃ 2. Altitude ≤ 1500m; 3. Relative humidity: the daily average is not greater than 95%, the monthly average is not greater than 90%, the daily average of saturated steam is not greater than 2.2*10-³Mpa, and the monthly average is not greater than 1.8*10-³Mpa; 4. The earthquake intensity does not exceed 8 degrees; 5. Places free of fire, explosion hazards, severe pollution, chemical corrosion and severe vibrations. Features 1. Ad...
ZN63M-12 (Magnetic type) Indoor Vacuum Circuit ...
Selection ZN63M - 12 P M 630 - 25 HT P210 Name Rated voltage(KV) Pole type Operating mechanism Rated current(A) Rated short-circuit breaking current(KA) Installation Phase spacing Indoor vacuum circuit breaker 12:12KV No mark: Insulating cylinder type P Solid -sealing type M: Insulating cylinder type permanent magne 630, 1250, 1600, 2000, 2500, 3150, 4000 20, 25, 31.5, 40 HT: Handcart FT: Fixed type P150, P210, P275 Note: The phase spacing of ZN63-12□M is usually P210mm, whic...
FZW32-12(40.5) Outdoor Vacuum Load Switch
Selection Features FZW32-12 (40.5) type outdoor high voltage isolating vacuum load switch adopts the vacuum arc extinguish chamber, no explosion danger, no maintenance. The load switch isolation knife linkage with a three-phase vacuum interrupter, breaking and closing operation in good same period, and with reliable isolation fracture when breaking, namely has the function of isolation switch. Most of the switch body parts are made of stainless steel materials, the base frame is made by stai...
RN2 Indoor Current Limiting Fuse
Technical data Product type RN2-3、6、10 RN2-15、20 RN2-35 Rated voltage 3 6 10 15 20 35 KV Fuse current A 0.5 0.5 0.5 Capacity of largest break of three-phase MVA 500 1000 1000 1000 Max break curent KA effective value KA 500 85 50 40 30 17 Overvoltage multiple Do not exceed voltage of 2.5 times of rating Resistance of the fuse pipe (Ω) 93±7 200±10 315土14 Weight Kg 5.6 12.2 15.6 Fuse weight Kg 0.9 1.6 2.5 Overall and mounting dimensions(mm)
GW9 Outdoor Isolation Switch
Selection Operating conditions 1. The altitude does not exceed 1000m. 2. The ambien t air temperature: Maximum+40℃: Minimum: General Area-30℃, Paramos-40℃ . 3. The wind pressure does not exceed 700Pa. 4. The earthquake intensity does not exceed 8 degrees. 5. The working situation without frequent violent vibration. 6. The installation site of ordinary type isolator s hould be kept away from gas,smoke chemical deposition, salt-spray-fog, dust and other and corrosive maters that affect serious...
ZW8-12 Outdoor Vacuum Circuit Breaker
Selection Operating conditions 1. Ambient temperature: upper limit +40℃, lower limit -30℃; 2. Altitude ≤ 2000 meters 3. Pressure: not more than 700Pa (corresponding to the wind speed 34m/s); 4. Earthquake intensity: do not exceed 8 degree; 5. Pollution grade: III class; 6. Maximum daily temperature variety less than 25℃. Technical data Item Unit Parameter Voltage, current parameters Rated voltage kV 12 Rated short time power frequency withstand voltage (1min) kV 42 Rated lightn...