LCT Current Transformer
Technical data 1. Operating environment a. Environmental temperature: -20℃~50℃; b. Relative humidity: ≤90% c. Atmospheric pressure: 80kpa~200kpa; 2. AC voltage: 66kV~4000kV; 3. Zero-sequence current:Primary side~36A (customize for 36A or above, secondary side 20~30mA) 4. Electric network frequence: 50Hz; 5. The terminal used with ML98 device-using explanation; System primary zero-sequence current(A) Selected terminal 1≤10<6 S1, S2 6≤10<12 S1, S3 12≤10<36 S1, S4 6. Secondary loa...
FXB Polymer Insulators
Technical data Type Ratde current (kv) Ratde machincal load(kN) Height (mm) Insulating Li(mm) FXBW2-12/70UC 12 70 350 180 FXB2-15/70UD 15 70 375 200 FXB2-24/70UD 24 70 430 290 FXB2-28/70UD 28 70 430 290 FXB2-33/70UD 33 70 550 360 FXB2-35/70UD 36 70 570 400 FXBO2-36/70 36 70 650 450 Type Min. creepage distance (mm) Diameter of shed D.(mm) Full wave lighting requency wet withsand vltage (peak)KV 1min Power requency wet withstand voltage (peak value)KV FXBW2-12/70UC...
JN15-12 Indoor Grounding Switch
Selection Operating conditions 1. Ambient temperature:-10~+40℃ 2. Altitude: ≤1000m (sensor height:140mm) 3. Relative humidity: Day average relative humidity ≤95% Month average relative humidity ≤90% 4. Earthquake intensity: ≤8degree 5. Dirtiness degree: II Technical data Item Units Data Rated voltage kV 12 Rated short time withstand current kA 31.5 Rated short circuit withstand time s 4 Rated short circuit making current kA 80 Rated peak withstand current kA 80 Rated 1min powe...
XRNT Current-limiting Fuses for Transformer Pro...
Selection Technical data Type Rated voltage Rated current of the fuse (A) Rated current of the fuselink (A) XRNT-12 12 40 3.15、6.3、10、16、20、25、31.5、40 XRNT-12 12 100 50、63、71、80、100、(125) XRNT-12 12 125 125、160、200、250 XRNT-24 24 200 3.15、6.3、10、16、20、25、31.5、40、50、63、80、100、125、160、200 XRNT–40.5 40.5 125 3.15、6.3、10、16、20、25、31.5、40、50、63、80、100、125、160、200 Overall and mounting dimensions(mm) Chat1/a link XRNT-12Kv Chat2/a li...
ZN63(VS1)-12 Indoor Vacuum Circuit Breaker (Ins...
Selection ZN63 - 12 T 630 - 25 HT P210 Model Rated voltage(KV) Operating mechanism Rated current(A) Rated short-circuit breaking current(KA) Installation Phase spacing Indoor vacuum circuit breaker 12:12KV T: Spring type 630,1250, 1600,2000, 2500, 3150, 4000 20, 25, 31.5, 40 HT: Handcart FT: Fixed type P150, P210, P275 Note: ZN63-12 adopts a double spring integrated mechanism by default. If a single spring modular mechanism is required, a single spring needs to be added to the mod...
FZN25/FZRN25-12 Indoor Vacuum Load Switch
Selection Operating conditions 1. Ambient air temperature: upper limit +40℃, lower limit -25℃ (allow storage at – 30℃), 24h average value is not higher than +35℃; 2. Altitude: no more than 1000m; 3. Relative humidity: daily average value is not greater than 95%, monthly average is not greater than 90%; 4. Earthquake intensity: do not exceed 8 degree; 5. The surrounding air is not corrosive and flammable gas,steam and other significant pollution; 6. No regular violent vibration; 7. Cont...