XL Low Voltage Power Distribution Cabinet
Selection Operating conditions 1. Environmental Conditions1.Installation Site: Indoor; 2. Altitude: No more than 2000m. 3. Earthquake lntensity: No more than 8 degrees. 4. Ambient Temperature: No more than +40℃ and no less than -15℃ . Averagetemperature is no more than +35℃ within 24 hours. 5. Relative Humidity: the average daily value is no more than 95%, the averagemonthly value is no more than 90%. 6. Installation locations: without fire,explosion danger,serious pollution,chemical corros...
ZW32-12 Outdoor Vacuum Circuit Breaker
Selection Operating conditions 1. The environment temperature: upper limit +40℃, lower limit -30℃ 2. Altitude ≤ 2000 meters 3. Wind pressure: no more than 700Pa (corresponding to the wind speed 34m/s) 4. Earthquake intensity: do not exceed 8 degree 5. Pollution grade: III class 6. Maximum daily temperature: less than 25℃ . Technical data Item Unit Parameter Voltage, current parameters Rated voltage kV 12 Rated short time power frequency withstand voltage (1min) kV 42/48 Rated l...
JN15-12 Indoor Grounding Switch
Selection Operating conditions 1. Ambient temperature:-10~+40℃ 2. Altitude: ≤1000m (sensor height:140mm) 3. Relative humidity: Day average relative humidity ≤95% Month average relative humidity ≤90% 4. Earthquake intensity: ≤8degree 5. Dirtiness degree: II Technical data Item Units Data Rated voltage kV 12 Rated short time withstand current kA 31.5 Rated short circuit withstand time s 4 Rated short circuit making current kA 80 Rated peak withstand current kA 80 Rated 1min powe...
GW4 Outdoor Isolation Switch
Selection Technical data Item Unit Parameters GW4- 40.5 GW4- 72.5 GW4- 126 GW4- 126G GW4- 145 Rated voltage KV 40.5 72.5 126 126 145 Rated current A 630 1250 2000 2500 630 1250 2000 2500 4000 630 1250 2000 2500 630 1250 1250 2000 2500 Rated short-time withstand current (RMS) KA 20 31.5 40(46) 20 31.5 40(46) 20 31.5 40(46) 20 31.5 20 31.5 40(46) Rated peak withstand current (peak) KA 50 80 100(104) 50 80 100(104) 50 80 100(104) 50 80 50 80 100(104) Rated short-time withstand...
ZN28-12 Indoor Vacuum Circuit Breaker
Selection Operating conditions 1. The environment temperature: upper limit +40℃, lower limit -15℃; 2. Altitude: ≤2000m; 3. Relative humidity: daily average value is not greater than 95%, monthly average is not greater than 90%; 4. Earthquake intensity: less than 8 degrees; 5. No fire, explosion, pollution, chemical corrosion and severe vibration place. Technical data Item Unit Parameter Parameters of voltage, current, life Rated voltage kV 12 Rated short time power frequency with...
ZW8-12 Outdoor Vacuum Circuit Breaker
Selection Operating conditions 1. Ambient temperature: upper limit +40℃, lower limit -30℃; 2. Altitude ≤ 2000 meters 3. Pressure: not more than 700Pa (corresponding to the wind speed 34m/s); 4. Earthquake intensity: do not exceed 8 degree; 5. Pollution grade: III class; 6. Maximum daily temperature variety less than 25℃. Technical data Item Unit Parameter Voltage, current parameters Rated voltage kV 12 Rated short time power frequency withstand voltage (1min) kV 42 Rated lightn...