SC(B)9 Series Epoxy Resin Dry-type Transformer
Selection Operating conditions 1. Ambient temperature: maximum temperature: +40°C, minimum temperature: -25℃ . 2. Average temperature of the hottest month:+30℃, average temperature in the hottest year:+20℃ . 3. Altitude not exceeding 1000m. 4. The waveform of the power supply voltage is similar to a sine wave. 5. The three-phase supply voltage should be approximately symmetrical. 6. The relative humidity of the surrounding air should be lower than 93%. 7. And there ...
XRNM1 Current-Limiting Fuses for Motor Protection
Selection Technical data Rated voltage(Kv) Rated break current KA Rated current of the fuse (A) Rated current of the fuse link (A) Major dimensions A B C D XRNM1-3.6 3.6 50 125 50,63,100,125 337(390) 254(312) 305(340) 51 200 125,160,200 76 400 250,315,355,400 XRNM1-7.2 7.2 12 160 25,31.5,40,50,63,80,100,125,160 486(500) 403(461) 454(150) 76 315 200,224,250,315 Note: 1. The aboveid rated parameters for single pipe, the fuses can be parallel connected by on-site ...
FZN21/FZRN21-12 Indoor Vacuum Load Switch
Selection Operating conditions 1. Altitude: no more than 1000m; 2. The environment temperature: upper limit +40℃, lower limit -30℃; 3. Relative humidity: daily average value is not greater than 95%, monthly average is not greater than 90%; 4. Saturated steam pressure: daily average value is not higher than 2.2×10 -3 Mpa, monthly average is not higher than 1.8×10 -3 Mpa; 5. No severe vibration, no corrosive gas, no fire, no explosion danger place. Technical data Item Unit Parameter Techn...
JN17 Indoor Grounding Switch
Selection Operating conditions 1. Ambient temperature:-10~+40℃ 2. Altitude: ≤1000m (sensor height:140mm) 3. Relative humidity: Day average relative humidity ≤95% Month average relative humidity ≤90% 4. Earthquake intensity: ≤8degree 5. Dirtiness degree: II Technical data Item Units Data Rated voltage kV 12 Rated short time withstand current kA 40 Rated short circuit withstand time s 4 Rated short circuit making current kA 100 Rated peak withstand curren...
JXF Low-voltage Integrated Distribution Box
Selection Operating conditions 1. Installation Site: Indoor or outdoor; 2. Atitude: No more than 2000m. 3. Earthquake lntensity: No more than 8 degrees. 4. Ambient Temperature: No more than +40℃ and no less than -25℃.Averagetemperature is no more than +35℃ within 24 hours. 5. Relative Humidity: the average daily value is no more than 95%, the averagemonthly value is no more than 90%. 6. Installation locations: without fire,explosion danger,serious pollution,chemical corrosion and violent vi...
XRNT Current-limiting Fuses for Transformer Pro...
Selection Technical data Type Rated voltage Rated current of the fuse (A) Rated current of the fuselink (A) XRNT-12 12 40 3.15、6.3、10、16、20、25、31.5、40 XRNT-12 12 100 50、63、71、80、100、(125) XRNT-12 12 125 125、160、200、250 XRNT-24 24 200 3.15、6.3、10、16、20、25、31.5、40、50、63、80、100、125、160、200 XRNT–40.5 40.5 125 3.15、6.3、10、16、20、25、31.5、40、50、63、80、100、125、160、200 Overall and mounting dimensions(mm) Chat1/a link XRNT-12Kv Chat2/a li...