ZN85-40.5 Indoor Vacuum Circuit Breaker
Selection Operating conditions 1. Ambient temperature -10℃ ~ +40℃ 2. Altitude ≤ 1500m; 3. Relative humidity: the daily average is not greater than 95%, the monthly average is not greater than 90%, the daily average of saturated steam is not greater than 2.2*10-³Mpa, and the monthly average is not greater than 1.8*10-³Mpa; 4. The earthquake intensity does not exceed 8 degrees; 5. Places free of fire, explosion hazards, severe pollution, chemical corrosion and severe vibrations. Features 1. Ad...
RN1 Indoor Current Limiting Fuse
Features Current which passes the fuse when being1.3 times of itsspecified electric current,Do not fusing for an hour; Whenthe current through the fuse is 2 times of its specinedelectric current,fusing in an hour;Refer to its fusingfeature curve in chart 1when select the fuse. Figure 1 RN1/RN3“An-second” characteristic curve Technical data 3 6 10 35 Rated current (A) 20 100 200 300 400 200 75 100 200 300 20 50 75 100 200 7.5 10 20 30 40 Max breaking curent KV effective vakue 40 1.3...
GGD Low Voltage Power Distribution Cabinet
Selection Operating conditions 1. Ambient air temperature: -15℃ ~+40℃ Daily average temperature: ≤35℃ When the actual temperature exceed the range, it should be used by reducing the capacity accordingly. 2. Transport and store temperature: -25℃ ~+55℃ . do not exceed +70℃ in short time. 3. Altitude: ≤2000m 4. Relative humidity: ≤50%, when temperature is +40℃ When temperature is low, larger relative humidity is allowed. when it is +20℃, relative humidity can be 90%. Since the temperature chang...
ZW32-12 Outdoor Vacuum Circuit Breaker
Selection Operating conditions 1. The environment temperature: upper limit +40℃, lower limit -30℃ 2. Altitude ≤ 2000 meters 3. Wind pressure: no more than 700Pa (corresponding to the wind speed 34m/s) 4. Earthquake intensity: do not exceed 8 degree 5. Pollution grade: III class 6. Maximum daily temperature: less than 25℃ . Technical data Item Unit Parameter Voltage, current parameters Rated voltage kV 12 Rated short time power frequency withstand voltage (1min) kV 42/48 Rated l...
GW4 Outdoor Isolation Switch
Selection Technical data Item Unit Parameters GW4- 40.5 GW4- 72.5 GW4- 126 GW4- 126G GW4- 145 Rated voltage KV 40.5 72.5 126 126 145 Rated current A 630 1250 2000 2500 630 1250 2000 2500 4000 630 1250 2000 2500 630 1250 1250 2000 2500 Rated short-time withstand current (RMS) KA 20 31.5 40(46) 20 31.5 40(46) 20 31.5 40(46) 20 31.5 20 31.5 40(46) Rated peak withstand current (peak) KA 50 80 100(104) 50 80 100(104) 50 80 100(104) 50 80 50 80 100(104) Rated short-time withstand...
RN2 Indoor Current Limiting Fuse
Technical data Product type RN2-3、6、10 RN2-15、20 RN2-35 Rated voltage 3 6 10 15 20 35 KV Fuse current A 0.5 0.5 0.5 Capacity of largest break of three-phase MVA 500 1000 1000 1000 Max break curent KA effective value KA 500 85 50 40 30 17 Overvoltage multiple Do not exceed voltage of 2.5 times of rating Resistance of the fuse pipe (Ω) 93±7 200±10 315土14 Weight Kg 5.6 12.2 15.6 Fuse weight Kg 0.9 1.6 2.5 Overall and mounting dimensions(mm)