GW9 Outdoor Isolation Switch
Selection Operating conditions 1. The altitude does not exceed 1000m. 2. The ambien t air temperature: Maximum+40℃: Minimum: General Area-30℃, Paramos-40℃ . 3. The wind pressure does not exceed 700Pa. 4. The earthquake intensity does not exceed 8 degrees. 5. The working situation without frequent violent vibration. 6. The installation site of ordinary type isolator s hould be kept away from gas,smoke chemical deposition, salt-spray-fog, dust and other and corrosive maters that affect serious...
ZN63(VS1)-12S Indoor Vacuum Circuit Breaker (P...
Selection ZN63(VS1) - 12 P T 630 - 25 HT P210 Name Rated voltage(KV) Pole type Operating mechanism Rated current(A) Rated short-circuit breaking current(KA) Installation Phase spacing Indoor vacuum circuit breaker 12:12KV P:Solid -sealing type T: Spring type 630, 1250, 1600, 2000, 2500, 3150, 4000 20, 25, 31.5, 40 HT: Handcart FT: Fixed type P150, P210, P275 Note: ZN63(VS1)-12P adopts a double spring integrated mechanism by default. If a single spring...
ZN63 (VS1)-12C Vacuum Circuit Breaker (Side-Ope...
Selection ZN63 C - 12 P / T 630 - 25 FT R P210 Name Structure - Rated voltage(KV) Pole type / Operating mechanism Rated current(A) - Rated short-circuit breaking current(KA) Installation Main circuit wiring direction Phase distance Indoor vacuum circuit breaker Side operation - 12:12KV No mark: Insulating cylinder type P: Solid-sealing type / T:Spring type 630 1250 1600 2000 2500 3150 4000 - 20 25 31.5 40 FT: Fixed type L: Left R: Right P210 Note: 1. order a ZN63 si...
FZSW Polymer Insulators
Technical data Type Ratde current (kv) Ratde machincal load(kN) Height (mm) Insulating Li(mm) FZSW-12/4 12 4 215±10 175 FZS-35/6 35 6 445±10 378 FZSW-35/6 35 6 450±10 360 FZSW-66/8 66 8 770±10 670 FZSW-110/10 110 10 1220±10 1085 Type Min. creepage distance (mm) Diameter of shed D.(mm) Full wave lighting requency wet withsand vltage (peak)KV 1min Power requency wet withstand voltage (peak value)KV FZSW-12/4 305 105/80 75 42 FZS-35/6 890 135...
FLN36 Indoor SF6 Load Switch
Selection Operating conditions 1. Air temperature Maximum temperature: +40℃; Minimum temperature:-35℃. 2. Humidity Monthly average humidity 95%; Daily average humidity 90%. 3. Altitude above sea level Maximum installation altitude: 2500m. 4. Ambient air not apparently polluted by corrosive and flammable gas, vapor etc. 5. No frequent violent shake. Technical data Ratings Unit Value Rated voltage kV 12 24 40.5 Rated lighting impulse withstand voltage kV 75 125 170 Common value Acro...
ZN23-40.5 Indoor Vacuum Circuit Breaker
Selection Operating conditions 1. The environment temperature: upper limit +40℃, lower limit -15℃ (cold area -25℃); 2. Altitude: not more than 2000m; 3. Relative humidity: daily average value is not greater than 95%, monthly average is not greater than 90%; 4. Saturated steam pressure: daily average value is not higher than 2.2 × 10 -3 Mpa,monthly average is not higher than 1.8×10-3 Mpa; 5. Earthquake intensity does not exceed 8 degrees; 6. No fire, explosion, pollution, chemical corrosion a...