LZZBJ10 Current Transformer
Selection Technical data 1. The performance of products is conformed to IEC standard and GB1208-2006 2. Current Transformer. 3. Rated insulation level: 12/42/75kV 4. Rated frequency: 50Hz 5. Rated secondary current: 5A, 1A 6. Partial discharge level: In conformity to GB5583-85 standard, its partial discharge is not more than 20PC. Rated primary current (A) Accurate class combination Rated secondary output(VA) Rated short-time thermal current (KA virtual value) Rated dynamic stability curr...
ZN63(VS1)-12 Indoor Vacuum Circuit Breaker (Ins...
Selection ZN63 - 12 T 630 - 25 HT P210 Model Rated voltage(KV) Operating mechanism Rated current(A) Rated short-circuit breaking current(KA) Installation Phase spacing Indoor vacuum circuit breaker 12:12KV T: Spring type 630,1250, 1600,2000, 2500, 3150, 4000 20, 25, 31.5, 40 HT: Handcart FT: Fixed type P150, P210, P275 Note: ZN63-12 adopts a double spring integrated mechanism by default. If a single spring modular mechanism is required, a single spring needs to be added to the mod...
JN15-12 Indoor Grounding Switch
Selection Operating conditions 1. Ambient temperature:-10~+40℃ 2. Altitude: ≤1000m (sensor height:140mm) 3. Relative humidity: Day average relative humidity ≤95% Month average relative humidity ≤90% 4. Earthquake intensity: ≤8degree 5. Dirtiness degree: II Technical data Item Units Data Rated voltage kV 12 Rated short time withstand current kA 31.5 Rated short circuit withstand time s 4 Rated short circuit making current kA 80 Rated peak withstand current kA 80 Rated 1min powe...
YRM6-12/24 Gas-insulated Metal-enclosed Switchgear
Selection Operating conditions 1. Ambient air temperature: -40℃~+40℃; 2. Relative air humidity: daily average <95%, monthly average <90%; 3. Altitude ≤1500m (under standard inflation pressure); 4. Seismic intensity <9 class; 5. Places free from fire, explosion, serious contamination, chemical corrosion and severe vibration. Special conditions Manufacturers and end users must agree on special Operating conditions that are different from normal operating cond...
KYN28-24 Metalclad AC Enclosed Switchgear, With...
Selection Operating conditions 1. +15°C~+40°C. And the average value measured within 24 hours shall not exceed 35°C 2. The average monthly relative humidity shall not exceed 90% The average monthly water vapor pressure shall not exceed 1.8kPa; 3. Altitude: ≤1000m. 4. There is no obvious dust or smoke in the surrounding air: pollution caused by corrosive or combustible gases, vapors, or salt mist; 5. Vibration or ground motion from outside the switchgear and control equipment can be ignored; ...
ZW8-12 Outdoor Vacuum Circuit Breaker
Selection Operating conditions 1. Ambient temperature: upper limit +40℃, lower limit -30℃; 2. Altitude ≤ 2000 meters 3. Pressure: not more than 700Pa (corresponding to the wind speed 34m/s); 4. Earthquake intensity: do not exceed 8 degree; 5. Pollution grade: III class; 6. Maximum daily temperature variety less than 25℃. Technical data Item Unit Parameter Voltage, current parameters Rated voltage kV 12 Rated short time power frequency withstand voltage (1min) kV 42 Rated lightn...