VYF-12GD Indoor Three Position Vacuum Circuit B...
Selection Note: If there is no grounding switch, the grounding operation shaft acts as an interlocking shaft, and the external dimensions remain unchanged. Operating conditions ● Ambient temperature: -25℃ +40℃; ● Relative humidity: daily average <95%, monthly average <90%; ● Altitude: not higher than 1000m; ● Earthquake intensity: no more than 8 degrees: ● Place of use: No explosion hazard, chemical and severe vibration and pollution. ● Service conditions above an altitude of 1000 mete...
ZW32-12 Outdoor Vacuum Circuit Breaker
Selection Operating conditions 1. The environment temperature: upper limit +40℃, lower limit -30℃ 2. Altitude ≤ 2000 meters 3. Wind pressure: no more than 700Pa (corresponding to the wind speed 34m/s) 4. Earthquake intensity: do not exceed 8 degree 5. Pollution grade: III class 6. Maximum daily temperature: less than 25℃ . Technical data Item Unit Parameter Voltage, current parameters Rated voltage kV 12 Rated short time power frequency withstand voltage (1min) kV 42/48 Rated l...
FN AC High-voltage Load Switch
Selection Technical data Rated voltage(kV) Highest voltage(kV) Rated current(A) Industrial frequency voltage withstand in 1min(kV) 4S thermal stable current (effective value)(A) 12 12 400 42/48 12.5 12 12 630 42/48 20 Active stable current (peak value)(A) Short circuit close current (A) Rated open current (A) Rated transfer current (A) 31.5 31.5 400 1000 50 50 630 1000 Type Full type DS Earthing switch at inlet position DX Earthing switch at inlet position L Interlock...
ZN85-40.5 Indoor Vacuum Circuit Breaker
Selection Operating conditions 1. Ambient temperature -10℃ ~ +40℃ 2. Altitude ≤ 1500m; 3. Relative humidity: the daily average is not greater than 95%, the monthly average is not greater than 90%, the daily average of saturated steam is not greater than 2.2*10-³Mpa, and the monthly average is not greater than 1.8*10-³Mpa; 4. The earthquake intensity does not exceed 8 degrees; 5. Places free of fire, explosion hazards, severe pollution, chemical corrosion and severe vibrations. Features 1. Ad...
XRNM1 Current-Limiting Fuses for Motor Protection
Selection Technical data Rated voltage(Kv) Rated break current KA Rated current of the fuse (A) Rated current of the fuse link (A) Major dimensions A B C D XRNM1-3.6 3.6 50 125 50,63,100,125 337(390) 254(312) 305(340) 51 200 125,160,200 76 400 250,315,355,400 XRNM1-7.2 7.2 12 160 25,31.5,40,50,63,80,100,125,160 486(500) 403(461) 454(150) 76 315 200,224,250,315 Note: 1. The aboveid rated parameters for single pipe, the fuses can be parallel connected by on-site ...
ZN63M-12 (Magnetic type) Indoor Vacuum Circuit ...
Selection ZN63M - 12 P M 630 - 25 HT P210 Name Rated voltage(KV) Pole type Operating mechanism Rated current(A) Rated short-circuit breaking current(KA) Installation Phase spacing Indoor vacuum circuit breaker 12:12KV No mark: Insulating cylinder type P Solid -sealing type M: Insulating cylinder type permanent magne 630, 1250, 1600, 2000, 2500, 3150, 4000 20, 25, 31.5, 40 HT: Handcart FT: Fixed type P150, P210, P275 Note: The phase spacing of ZN63-12□M is usually P210mm, whic...Medium and high voltage products are electrical equipment designed to handle voltages above the standard household voltage of 120V. These products are used in a variety of applications, including power generation, transmission, and distribution, as well as industrial and commercial settings.