FZW28-12F Outdoor Vacuum Load Switch
Selection Operating conditions 1. Altitude: ≤ 2000 meters; 2. Environment temperature: -40℃ ~+85℃; 3. Relative humidity: ≤ 90% (25℃); 4. The maximum daily temperature difference: 25℃; 5. Protection grade: IP67; 6. The maximum ice thickness: 10mm. Technical data Item Unit Parameter The switch body Rated voltage kV 12 Power frequency insulation withstand voltage (Interphase and phase to ground / fracture) kV 42/48 Lightning impulse withstand voltage (Interphase and phase to groun...
ZN28-12 Indoor Vacuum Circuit Breaker
Selection Operating conditions 1. The environment temperature: upper limit +40℃, lower limit -15℃; 2. Altitude: ≤2000m; 3. Relative humidity: daily average value is not greater than 95%, monthly average is not greater than 90%; 4. Earthquake intensity: less than 8 degrees; 5. No fire, explosion, pollution, chemical corrosion and severe vibration place. Technical data Item Unit Parameter Parameters of voltage, current, life Rated voltage kV 12 Rated short time power frequency with...
RN2 Indoor Current Limiting Fuse
Technical data Product type RN2-3、6、10 RN2-15、20 RN2-35 Rated voltage 3 6 10 15 20 35 KV Fuse current A 0.5 0.5 0.5 Capacity of largest break of three-phase MVA 500 1000 1000 1000 Max break curent KA effective value KA 500 85 50 40 30 17 Overvoltage multiple Do not exceed voltage of 2.5 times of rating Resistance of the fuse pipe (Ω) 93±7 200±10 315土14 Weight Kg 5.6 12.2 15.6 Fuse weight Kg 0.9 1.6 2.5 Overall and mounting dimensions(mm)
JN22-40.5/31.5 Indoor Grounding Switch
Selection Operating conditions 1. Ambient temperature:-10~+40℃ 2. Altitude: ≤1000m 3. Relative humidity: Day average relative humidity ≤95% Month average relative humidity ≤90% 4. Earthquake intensity: ≤8degree 5. Appliable in the place without corrosive, flammable gas and water place 6. With no frequently intense vibrant place around. Technical data Item Units Data Rated voltage kV 35 Maximum voltage kV 40.5 Rated short time withstand current kA 31.5 Rat...
LZZBJ10 Current Transformer
Selection Technical data 1. The performance of products is conformed to IEC standard and GB1208-2006 2. Current Transformer. 3. Rated insulation level: 12/42/75kV 4. Rated frequency: 50Hz 5. Rated secondary current: 5A, 1A 6. Partial discharge level: In conformity to GB5583-85 standard, its partial discharge is not more than 20PC. Rated primary current (A) Accurate class combination Rated secondary output(VA) Rated short-time thermal current (KA virtual value) Rated dynamic stability curr...
FLN36 Indoor SF6 Load Switch
Selection Operating conditions 1. Air temperature Maximum temperature: +40℃; Minimum temperature:-35℃. 2. Humidity Monthly average humidity 95%; Daily average humidity 90%. 3. Altitude above sea level Maximum installation altitude: 2500m. 4. Ambient air not apparently polluted by corrosive and flammable gas, vapor etc. 5. No frequent violent shake. Technical data Ratings Unit Value Rated voltage kV 12 24 40.5 Rated lighting impulse withstand voltage kV 75 125 170 Common value Acro...Medium and high voltage products are electrical equipment designed to handle voltages above the standard household voltage of 120V. These products are used in a variety of applications, including power generation, transmission, and distribution, as well as industrial and commercial settings.