VYF-12GD Indoor Three Position Vacuum Circuit B...
Selection Note: If there is no grounding switch, the grounding operation shaft acts as an interlocking shaft, and the external dimensions remain unchanged. Operating conditions ● Ambient temperature: -25℃ +40℃; ● Relative humidity: daily average <95%, monthly average <90%; ● Altitude: not higher than 1000m; ● Earthquake intensity: no more than 8 degrees: ● Place of use: No explosion hazard, chemical and severe vibration and pollution. ● Service conditions above an altitude of 1000 mete...ZN63(VS1)-12S Indoor Vacuum Circuit Breaker (P...
Selection ZN63(VS1) - 12 P T 630 - 25 HT P210 Name Rated voltage(KV) Pole type Operating mechanism Rated current(A) Rated short-circuit breaking current(KA) Installation Phase spacing Indoor vacuum circuit breaker 12:12KV P:Solid -sealing type T: Spring type 630, 1250, 1600, 2000, 2500, 3150, 4000 20, 25, 31.5, 40 HT: Handcart FT: Fixed type P150, P210, P275 Note: ZN63(VS1)-12P adopts a double spring integrated mechanism by default. If a single spring...ZW32-24 Outdoor Vacuum Circuit Breaker
Selection Operating conditions 1. Ambient air temperature: The daily temperature variation: -40℃ ~+40℃ diurnal variation of temperature less than 25℃; 2. Altitude: no more than 2000 meters 3. Wind speed is no more than 35m/s (equivalent to 700Pa on the surface of the cylindrical); 4. Ice cover thickness no more than 10mm; 5. The intensity of sunshine not more than 1000W/m ² 6. Pollution degree no more than GB 5582 IV class 7. Seismic intensity does not exceed 8 class 8. No flammable, explosi...ZW20-12 Outdoor Vacuum Circuit Breaker
Selection Operating conditions 1. Altitude≤2000 meters 2. The environment temperature: -30℃ ~+55℃ outdoor; the highest annual average temperature 20 ℃, the highest daily average temperature 30 ℃; 3. Relative humidity: 95% (25℃) 4. Seismic capacity: horizontal ground acceleration 0.3g, vertical ground acceleration 0.15g, at the same time duration of three sine waves, a safety factor of 1.67 5. Earthquake intensity: 7 degrees 6. The maximum daily temperature difference: 25 ℃ 7. The intensity o...ZN63 (VS1)-12C Vacuum Circuit Breaker (Side-Ope...
Selection ZN63 C - 12 P / T 630 - 25 FT R P210 Name Structure - Rated voltage(KV) Pole type / Operating mechanism Rated current(A) - Rated short-circuit breaking current(KA) Installation Main circuit wiring direction Phase distance Indoor vacuum circuit breaker Side operation - 12:12KV No mark: Insulating cylinder type P: Solid-sealing type / T:Spring type 630 1250 1600 2000 2500 3150 4000 - 20 25 31.5 40 FT: Fixed type L: Left R: Right P210 Note: 1. order a ZN63 si...ZW32-12 Outdoor Vacuum Circuit Breaker
Selection Operating conditions 1. The environment temperature: upper limit +40℃, lower limit -30℃ 2. Altitude ≤ 2000 meters 3. Wind pressure: no more than 700Pa (corresponding to the wind speed 34m/s) 4. Earthquake intensity: do not exceed 8 degree 5. Pollution grade: III class 6. Maximum daily temperature: less than 25℃ . Technical data Item Unit Parameter Voltage, current parameters Rated voltage kV 12 Rated short time power frequency withstand voltage (1min) kV 42/48 Rated l...