ZW8-12 Outdoor Vacuum Circuit Breaker
Selection Operating conditions 1. Ambient temperature: upper limit +40℃, lower limit -30℃; 2. Altitude ≤ 2000 meters 3. Pressure: not more than 700Pa (corresponding to the wind speed 34m/s); 4. Earthquake intensity: do not exceed 8 degree; 5. Pollution grade: III class; 6. Maximum daily temperature variety less than 25℃. Technical data Item Unit Parameter Voltage, current parameters Rated voltage kV 12 Rated short time power frequency withstand voltage (1min) kV 42 Rated lightn...
MNS Low-voltage Switchgear Panel, Withdrawable ...
Selection Operating conditions 1. lnstallation Site: Indoor; 2. Altitude: No more than 2000m. 3. Earthquake lntensity: No more than 8 degrees. 4. Ambient Temperature: No more than +40℃ and no less than -15℃.Averagetemperature is no more than +35℃ within 24 hours. 5. Pelative Humidity: the average daily value is no more than 95%, the averagemonthlyvalue is no more than 90%. 6. Installation lacations: without fire,explosion danger,serious pollution,chemical corrosion and violent vibration. Fe...
FZSW Polymer Insulators
Technical data Type Ratde current (kv) Ratde machincal load(kN) Height (mm) Insulating Li(mm) FZSW-12/4 12 4 215±10 175 FZS-35/6 35 6 445±10 378 FZSW-35/6 35 6 450±10 360 FZSW-66/8 66 8 770±10 670 FZSW-110/10 110 10 1220±10 1085 Type Min. creepage distance (mm) Diameter of shed D.(mm) Full wave lighting requency wet withsand vltage (peak)KV 1min Power requency wet withstand voltage (peak value)KV FZSW-12/4 305 105/80 75 42 FZS-35/6 890 135...
YSM6-12~24 Air-insulated RMU(Fixed Type)
Selection Operating conditions 1. Air temperature: Maximum temperature: +40℃; Minimum temperature:-5℃ 2. Humidity: Monthly average humidity 95%; Daily average humidity 90% . 3. Altitude above sea level: Maximum installation altitude: 2000m 4. Ambient air not apparently polluted by corrosive and flammable gas, vapor etc. 5. No frequent violent shake Features 1. Incoming unit with switch disconnector(Load break switch) schemas With other extra components optional Outg...
ZN63(VS1)-24 Indoor Vacuum Circuit Breaker
Selection ZN63 - 24 P / T 630 - 25 HT P210 Name - Rated voltage(KV) Pole type / Operating mechanism Rated current(A) breaking current(KA) - Rated short-circuit Installation Main circuit wiring direction Indoor vacuum circuit breaker - 24:24KV No mark: Insulating cylinder type P: Solid-sealing type / T: Spring type 630 1250 1600 2000 2500 3150 4000 - 20 25 31.5 40 HT:Handcart type FT:Fixed type P210 P275 Note: Zn63 (S) adopts a double spring integral mechanism by default. If...
HXGN15 Air-insulated RMU(Fixed Type)
Selection Operating conditions 1. Ambient air temperature: -15℃ ~+40℃ . Daily average temperature:≤35℃ . 2. Altitude: ≤1000m. 3. Relative humidity : Daily average≤95%, daily averange of vapour pressure≤2.2kpa Monthly average≤90%, monthly averange of vapour pressure≤1.8kpa. 4. Earthquake intensity: ≤magnitude 8. 5. Applicable in the places without corrosive and flammable gas. Note: Customized products are available. Technical data No. Item Unit Data 1 Rated voltage kV 12 2 Rated curren...