ZW32Y-12 Outdoor Vacuum Circuit Breaker
Selection Operating conditions 1. Ambient temperature: upper limit +40℃, lower limit -30℃; 2. Altitude: ≤2000m; 3. Wind pressure: not more than 700Pa (corresponding to the wind speed 34m/s); 4. Earthquake intensity: do not exceed 8 degree; 5. Pollution grade: III class; 6. Maximum daily temperature variety less than 25℃ . Technical data Item Unit Parameter Rated voltage kV 12 Rated insulation level 1min power frequency withstand voltage Dry test Wet test kV 42/ fracture 48 kV 34 ...
LFS-10Q Current Transformer
Selection Structural introduction This type of current transformer is fully enclosed and post type. It has a good ability of insulation, moisture proof and antipollution. It is small and light. It can be installed at any place and any direction. Technical data 1. Rated insulation level: 12/42/75kV; 2. Rated secondary current: 5A,1A; 3. Refer to the table for rated primary current, accuracy classed combination, rated output, rated dynamic and thermal current. 4. The conditions of partial disc...
XRNM1 Current-Limiting Fuses for Motor Protection
Selection Technical data Rated voltage(Kv) Rated break current KA Rated current of the fuse (A) Rated current of the fuse link (A) Major dimensions A B C D XRNM1-3.6 3.6 50 125 50,63,100,125 337(390) 254(312) 305(340) 51 200 125,160,200 76 400 250,315,355,400 XRNM1-7.2 7.2 12 160 25,31.5,40,50,63,80,100,125,160 486(500) 403(461) 454(150) 76 315 200,224,250,315 Note: 1. The aboveid rated parameters for single pipe, the fuses can be parallel connected by on-site ...
ZN63(VS1)-12 Indoor Vacuum Circuit Breaker (Ins...
Selection ZN63 - 12 T 630 - 25 HT P210 Model Rated voltage(KV) Operating mechanism Rated current(A) Rated short-circuit breaking current(KA) Installation Phase spacing Indoor vacuum circuit breaker 12:12KV T: Spring type 630,1250, 1600,2000, 2500, 3150, 4000 20, 25, 31.5, 40 HT: Handcart FT: Fixed type P150, P210, P275 Note: ZN63-12 adopts a double spring integrated mechanism by default. If a single spring modular mechanism is required, a single spring needs to be added to the mod...
ZW20-12 Outdoor Vacuum Circuit Breaker
Selection Operating conditions 1. Altitude≤2000 meters 2. The environment temperature: -30℃ ~+55℃ outdoor; the highest annual average temperature 20 ℃, the highest daily average temperature 30 ℃; 3. Relative humidity: 95% (25℃) 4. Seismic capacity: horizontal ground acceleration 0.3g, vertical ground acceleration 0.15g, at the same time duration of three sine waves, a safety factor of 1.67 5. Earthquake intensity: 7 degrees 6. The maximum daily temperature difference: 25 ℃ 7. The intensity o...
FZSW Polymer Insulators
Technical data Type Ratde current (kv) Ratde machincal load(kN) Height (mm) Insulating Li(mm) FZSW-12/4 12 4 215±10 175 FZS-35/6 35 6 445±10 378 FZSW-35/6 35 6 450±10 360 FZSW-66/8 66 8 770±10 670 FZSW-110/10 110 10 1220±10 1085 Type Min. creepage distance (mm) Diameter of shed D.(mm) Full wave lighting requency wet withsand vltage (peak)KV 1min Power requency wet withstand voltage (peak value)KV FZSW-12/4 305 105/80 75 42 FZS-35/6 890 135...