XL Low Voltage Power Distribution Cabinet
Selection Operating conditions 1. Environmental Conditions1.Installation Site: Indoor; 2. Altitude: No more than 2000m. 3. Earthquake lntensity: No more than 8 degrees. 4. Ambient Temperature: No more than +40℃ and no less than -15℃ . Averagetemperature is no more than +35℃ within 24 hours. 5. Relative Humidity: the average daily value is no more than 95%, the averagemonthly value is no more than 90%. 6. Installation locations: without fire,explosion danger,serious pollution,chemical corros...
JN15-24 Indoor Grounding Switch
Selection Operating conditions 1. Ambient temperature:-10~+40℃ 2. Altitude: ≤2000m 3. Relative humidity: Day average relative humidity ≤95% Month average relative humidity ≤90% 4. Earthquake intensity: ≤8degree 5. Class of pollution: II Technical data Item Units Data Rated voltage kV 24 Rated short time withstand current kA 31.5 Rated short circuit withstand time S 4 Rated short circuit making current kA 80 Rated peak withstand current kA 80 Rated 1min power frequency withstan...
GW9 Outdoor Isolation Switch
Selection Operating conditions 1. The altitude does not exceed 1000m. 2. The ambien t air temperature: Maximum+40℃: Minimum: General Area-30℃, Paramos-40℃ . 3. The wind pressure does not exceed 700Pa. 4. The earthquake intensity does not exceed 8 degrees. 5. The working situation without frequent violent vibration. 6. The installation site of ordinary type isolator s hould be kept away from gas,smoke chemical deposition, salt-spray-fog, dust and other and corrosive maters that affect serious...
ZN28-12 Indoor Vacuum Circuit Breaker
Selection Operating conditions 1. The environment temperature: upper limit +40℃, lower limit -15℃; 2. Altitude: ≤2000m; 3. Relative humidity: daily average value is not greater than 95%, monthly average is not greater than 90%; 4. Earthquake intensity: less than 8 degrees; 5. No fire, explosion, pollution, chemical corrosion and severe vibration place. Technical data Item Unit Parameter Parameters of voltage, current, life Rated voltage kV 12 Rated short time power frequency with...
XRNM1 Current-Limiting Fuses for Motor Protection
Selection Technical data Rated voltage(Kv) Rated break current KA Rated current of the fuse (A) Rated current of the fuse link (A) Major dimensions A B C D XRNM1-3.6 3.6 50 125 50,63,100,125 337(390) 254(312) 305(340) 51 200 125,160,200 76 400 250,315,355,400 XRNM1-7.2 7.2 12 160 25,31.5,40,50,63,80,100,125,160 486(500) 403(461) 454(150) 76 315 200,224,250,315 Note: 1. The aboveid rated parameters for single pipe, the fuses can be parallel connected by on-site ...
JN22-40.5/31.5 Indoor Grounding Switch
Selection Operating conditions 1. Ambient temperature:-10~+40℃ 2. Altitude: ≤1000m 3. Relative humidity: Day average relative humidity ≤95% Month average relative humidity ≤90% 4. Earthquake intensity: ≤8degree 5. Appliable in the place without corrosive, flammable gas and water place 6. With no frequently intense vibrant place around. Technical data Item Units Data Rated voltage kV 35 Maximum voltage kV 40.5 Rated short time withstand current kA 31.5 Rat...