ZN85-40.5 Indoor Vacuum Circuit Breaker
Selection Operating conditions 1. Ambient temperature -10℃ ~ +40℃ 2. Altitude ≤ 1500m; 3. Relative humidity: the daily average is not greater than 95%, the monthly average is not greater than 90%, the daily average of saturated steam is not greater than 2.2*10-³Mpa, and the monthly average is not greater than 1.8*10-³Mpa; 4. The earthquake intensity does not exceed 8 degrees; 5. Places free of fire, explosion hazards, severe pollution, chemical corrosion and severe vibrations. Features 1. Ad...
FN AC High-voltage Load Switch
Selection Technical data Rated voltage(kV) Highest voltage(kV) Rated current(A) Industrial frequency voltage withstand in 1min(kV) 4S thermal stable current (effective value)(A) 12 12 400 42/48 12.5 12 12 630 42/48 20 Active stable current (peak value)(A) Short circuit close current (A) Rated open current (A) Rated transfer current (A) 31.5 31.5 400 1000 50 50 630 1000 Type Full type DS Earthing switch at inlet position DX Earthing switch at inlet position L Interlock...
KYN61-40.5 Metalclad AC Enclosed Switchgear, Wi...
Selection Operating conditions 1. Ambient air temperature: -15℃ ~+40℃ 2. Altitude: ≤1000m 3. Relative humidity : Daily average≤95%; Monthly average≤90% 4. Earthquake intensity:≤magnitude 8. 5. Applicable in the places without corrosive and flammable gas. Note: Customized products are available. Features 1. The cabinet is made of aluminum-zinc coated sheet processed by CNC equipment and assembled with bolts or rivets, with a fully modular structure. 2. This switchgear has various functions to...
RN1 Indoor Current Limiting Fuse
Features Current which passes the fuse when being1.3 times of itsspecified electric current,Do not fusing for an hour; Whenthe current through the fuse is 2 times of its specinedelectric current,fusing in an hour;Refer to its fusingfeature curve in chart 1when select the fuse. Figure 1 RN1/RN3“An-second” characteristic curve Technical data 3 6 10 35 Rated current (A) 20 100 200 300 400 200 75 100 200 300 20 50 75 100 200 7.5 10 20 30 40 Max breaking curent KV effective vakue 40 1.3...
GGD Low Voltage Power Distribution Cabinet
Selection Operating conditions 1. Ambient air temperature: -15℃ ~+40℃ Daily average temperature: ≤35℃ When the actual temperature exceed the range, it should be used by reducing the capacity accordingly. 2. Transport and store temperature: -25℃ ~+55℃ . do not exceed +70℃ in short time. 3. Altitude: ≤2000m 4. Relative humidity: ≤50%, when temperature is +40℃ When temperature is low, larger relative humidity is allowed. when it is +20℃, relative humidity can be 90%. Since the temperature chang...
FXB Polymer Insulators
Technical data Type Ratde current (kv) Ratde machincal load(kN) Height (mm) Insulating Li(mm) FXBW2-12/70UC 12 70 350 180 FXB2-15/70UD 15 70 375 200 FXB2-24/70UD 24 70 430 290 FXB2-28/70UD 28 70 430 290 FXB2-33/70UD 33 70 550 360 FXB2-35/70UD 36 70 570 400 FXBO2-36/70 36 70 650 450 Type Min. creepage distance (mm) Diameter of shed D.(mm) Full wave lighting requency wet withsand vltage (peak)KV 1min Power requency wet withstand voltage (peak value)KV FXBW2-12/70UC...