GW9 Outdoor Isolation Switch
Selection Operating conditions 1. The altitude does not exceed 1000m. 2. The ambien t air temperature: Maximum+40℃: Minimum: General Area-30℃, Paramos-40℃ . 3. The wind pressure does not exceed 700Pa. 4. The earthquake intensity does not exceed 8 degrees. 5. The working situation without frequent violent vibration. 6. The installation site of ordinary type isolator s hould be kept away from gas,smoke chemical deposition, salt-spray-fog, dust and other and corrosive maters that affect serious...
GW4 Outdoor Isolation Switch
Selection Technical data Item Unit Parameters GW4- 40.5 GW4- 72.5 GW4- 126 GW4- 126G GW4- 145 Rated voltage KV 40.5 72.5 126 126 145 Rated current A 630 1250 2000 2500 630 1250 2000 2500 4000 630 1250 2000 2500 630 1250 1250 2000 2500 Rated short-time withstand current (RMS) KA 20 31.5 40(46) 20 31.5 40(46) 20 31.5 40(46) 20 31.5 20 31.5 40(46) Rated peak withstand current (peak) KA 50 80 100(104) 50 80 100(104) 50 80 100(104) 50 80 50 80 100(104) Rated short-time withstand...
RN2 Indoor Current Limiting Fuse
Technical data Product type RN2-3、6、10 RN2-15、20 RN2-35 Rated voltage 3 6 10 15 20 35 KV Fuse current A 0.5 0.5 0.5 Capacity of largest break of three-phase MVA 500 1000 1000 1000 Max break curent KA effective value KA 500 85 50 40 30 17 Overvoltage multiple Do not exceed voltage of 2.5 times of rating Resistance of the fuse pipe (Ω) 93±7 200±10 315土14 Weight Kg 5.6 12.2 15.6 Fuse weight Kg 0.9 1.6 2.5 Overall and mounting dimensions(mm)
YRM6-12/24 Gas-insulated Metal-enclosed Switchgear
Selection Operating conditions 1. Ambient air temperature: -40℃~+40℃; 2. Relative air humidity: daily average <95%, monthly average <90%; 3. Altitude ≤1500m (under standard inflation pressure); 4. Seismic intensity <9 class; 5. Places free from fire, explosion, serious contamination, chemical corrosion and severe vibration. Special conditions Manufacturers and end users must agree on special Operating conditions that are different from normal operating cond...
YSM6-12~24 Air-insulated RMU(Fixed Type)
Selection Operating conditions 1. Air temperature: Maximum temperature: +40℃; Minimum temperature:-5℃ 2. Humidity: Monthly average humidity 95%; Daily average humidity 90% . 3. Altitude above sea level: Maximum installation altitude: 2000m 4. Ambient air not apparently polluted by corrosive and flammable gas, vapor etc. 5. No frequent violent shake Features 1. Incoming unit with switch disconnector(Load break switch) schemas With other extra components optional Outg...
LFS-10Q Current Transformer
Selection Structural introduction This type of current transformer is fully enclosed and post type. It has a good ability of insulation, moisture proof and antipollution. It is small and light. It can be installed at any place and any direction. Technical data 1. Rated insulation level: 12/42/75kV; 2. Rated secondary current: 5A,1A; 3. Refer to the table for rated primary current, accuracy classed combination, rated output, rated dynamic and thermal current. 4. The conditions of partial disc...