ZW32Y-12 Outdoor Vacuum Circuit Breaker
Selection Operating conditions 1. Ambient temperature: upper limit +40℃, lower limit -30℃; 2. Altitude: ≤2000m; 3. Wind pressure: not more than 700Pa (corresponding to the wind speed 34m/s); 4. Earthquake intensity: do not exceed 8 degree; 5. Pollution grade: III class; 6. Maximum daily temperature variety less than 25℃ . Technical data Item Unit Parameter Rated voltage kV 12 Rated insulation level 1min power frequency withstand voltage Dry test Wet test kV 42/ fracture 48 kV 34 ...
GW4 Outdoor Isolation Switch
Selection Technical data Item Unit Parameters GW4- 40.5 GW4- 72.5 GW4- 126 GW4- 126G GW4- 145 Rated voltage KV 40.5 72.5 126 126 145 Rated current A 630 1250 2000 2500 630 1250 2000 2500 4000 630 1250 2000 2500 630 1250 1250 2000 2500 Rated short-time withstand current (RMS) KA 20 31.5 40(46) 20 31.5 40(46) 20 31.5 40(46) 20 31.5 20 31.5 40(46) Rated peak withstand current (peak) KA 50 80 100(104) 50 80 100(104) 50 80 100(104) 50 80 50 80 100(104) Rated short-time withstand...
ZN63(VS1)-12 Indoor Vacuum Circuit Breaker (Ins...
Selection ZN63 - 12 T 630 - 25 HT P210 Model Rated voltage(KV) Operating mechanism Rated current(A) Rated short-circuit breaking current(KA) Installation Phase spacing Indoor vacuum circuit breaker 12:12KV T: Spring type 630,1250, 1600,2000, 2500, 3150, 4000 20, 25, 31.5, 40 HT: Handcart FT: Fixed type P150, P210, P275 Note: ZN63-12 adopts a double spring integrated mechanism by default. If a single spring modular mechanism is required, a single spring needs to be added to the mod...
GW9 Outdoor Isolation Switch
Selection Operating conditions 1. The altitude does not exceed 1000m. 2. The ambien t air temperature: Maximum+40℃: Minimum: General Area-30℃, Paramos-40℃ . 3. The wind pressure does not exceed 700Pa. 4. The earthquake intensity does not exceed 8 degrees. 5. The working situation without frequent violent vibration. 6. The installation site of ordinary type isolator s hould be kept away from gas,smoke chemical deposition, salt-spray-fog, dust and other and corrosive maters that affect serious...
XRNM1 Current-Limiting Fuses for Motor Protection
Selection Technical data Rated voltage(Kv) Rated break current KA Rated current of the fuse (A) Rated current of the fuse link (A) Major dimensions A B C D XRNM1-3.6 3.6 50 125 50,63,100,125 337(390) 254(312) 305(340) 51 200 125,160,200 76 400 250,315,355,400 XRNM1-7.2 7.2 12 160 25,31.5,40,50,63,80,100,125,160 486(500) 403(461) 454(150) 76 315 200,224,250,315 Note: 1. The aboveid rated parameters for single pipe, the fuses can be parallel connected by on-site ...
LZZBJ10 Current Transformer
Selection Technical data 1. The performance of products is conformed to IEC standard and GB1208-2006 2. Current Transformer. 3. Rated insulation level: 12/42/75kV 4. Rated frequency: 50Hz 5. Rated secondary current: 5A, 1A 6. Partial discharge level: In conformity to GB5583-85 standard, its partial discharge is not more than 20PC. Rated primary current (A) Accurate class combination Rated secondary output(VA) Rated short-time thermal current (KA virtual value) Rated dynamic stability curr...