LFSB-10 Current Transformer
Selection Structural introduction This type of current transformer is fully enclosed and post type. It has a good ability of insulation, moisture proof and antipollution. It is small and light. It can be installed at any place and any direction. Technical data 1. Rated insulation level: 12/42/75kV; 2. Rated secondary current: 5A,1A; 3. Refer to the table for rated primary current, accuracy classed combination, rated output, rated dynamic and thermal current. 4. The conditions of partial disc...
JN22-40.5/31.5 Indoor Grounding Switch
Selection Operating conditions 1. Ambient temperature:-10~+40℃ 2. Altitude: ≤1000m 3. Relative humidity: Day average relative humidity ≤95% Month average relative humidity ≤90% 4. Earthquake intensity: ≤8degree 5. Appliable in the place without corrosive, flammable gas and water place 6. With no frequently intense vibrant place around. Technical data Item Units Data Rated voltage kV 35 Maximum voltage kV 40.5 Rated short time withstand current kA 31.5 Rat...
MNS Low-voltage Switchgear Panel, Withdrawable ...
Selection Operating conditions 1. lnstallation Site: Indoor; 2. Altitude: No more than 2000m. 3. Earthquake lntensity: No more than 8 degrees. 4. Ambient Temperature: No more than +40℃ and no less than -15℃.Averagetemperature is no more than +35℃ within 24 hours. 5. Pelative Humidity: the average daily value is no more than 95%, the averagemonthlyvalue is no more than 90%. 6. Installation lacations: without fire,explosion danger,serious pollution,chemical corrosion and violent vibration. Fe...
KYN28-12 Metalclad AC Enclosed Switchgear, With...
Selection Operating conditions 1. Ambient air temperature: -15℃ ~+40℃ . 2. Altitude: ≤1000m. 3. Relative humidity : Daily average≤95%, daily averange of vapour pressure≤2.2kpa. 4. Earthquake intensity: ≤magnitude 8. 5. Applicable in the places without corrosive and flammable gas and water vapor. 6. Used in place without frequently intense vibrant. Note: Customized products are available. Features 1. The cabinet is made of aluminum-zinc coated sheet processed by CNC equipment, andisassembled ...
RN2 Indoor Current Limiting Fuse
Technical data Product type RN2-3、6、10 RN2-15、20 RN2-35 Rated voltage 3 6 10 15 20 35 KV Fuse current A 0.5 0.5 0.5 Capacity of largest break of three-phase MVA 500 1000 1000 1000 Max break curent KA effective value KA 500 85 50 40 30 17 Overvoltage multiple Do not exceed voltage of 2.5 times of rating Resistance of the fuse pipe (Ω) 93±7 200±10 315土14 Weight Kg 5.6 12.2 15.6 Fuse weight Kg 0.9 1.6 2.5 Overall and mounting dimensions(mm)
GCS Low-voltage Switchgear Panel, Withdrawable ...
Selection Operating conditions 1. Ambient air temperature: -15℃ ~+40℃ Daily average temperature: ≤35℃ When the actual temperature exceed the range, it should be used by reducing the capacity accordingly. 2. Altitude: ≤2000m 3. Relative humidity: ≤50%, when temperature is +40℃ When temperature is low, larger relative humidity is allowed. when it is +20℃, relative humidity can be 90%. Since the temperature change will make out condensation. 4. Installation inclination: ≤5% 5. Applicable in the...