YB27-12/0.4 Outdoor Prefabricated Substation (US)
Selection Operating conditions 1. Ambient air temperature: -30℃ ~+40℃ 2. Altitude: ≤1000m 3. Wind speed:34m/s ≤700pa 4. Relative humidity: Daily average relative humidity ≤95%.Monthly average relative humidity ≤95%. 5. Installation inclination: ≤grade 8 6. Applicable in the places without corrosive and flammable gas. Note: Customized products are available. Features 1. Compact structure with small volume, the volume is 1/3-1/5 of European style substation in same capacity. It reduce the floo...
JN22-40.5/31.5 Indoor Grounding Switch
Selection Operating conditions 1. Ambient temperature:-10~+40℃ 2. Altitude: ≤1000m 3. Relative humidity: Day average relative humidity ≤95% Month average relative humidity ≤90% 4. Earthquake intensity: ≤8degree 5. Appliable in the place without corrosive, flammable gas and water place 6. With no frequently intense vibrant place around. Technical data Item Units Data Rated voltage kV 35 Maximum voltage kV 40.5 Rated short time withstand current kA 31.5 Rat...
GW4 Outdoor Isolation Switch
Selection Technical data Item Unit Parameters GW4- 40.5 GW4- 72.5 GW4- 126 GW4- 126G GW4- 145 Rated voltage KV 40.5 72.5 126 126 145 Rated current A 630 1250 2000 2500 630 1250 2000 2500 4000 630 1250 2000 2500 630 1250 1250 2000 2500 Rated short-time withstand current (RMS) KA 20 31.5 40(46) 20 31.5 40(46) 20 31.5 40(46) 20 31.5 20 31.5 40(46) Rated peak withstand current (peak) KA 50 80 100(104) 50 80 100(104) 50 80 100(104) 50 80 50 80 100(104) Rated short-time withstand...
RN2 Indoor Current Limiting Fuse
Technical data Product type RN2-3、6、10 RN2-15、20 RN2-35 Rated voltage 3 6 10 15 20 35 KV Fuse current A 0.5 0.5 0.5 Capacity of largest break of three-phase MVA 500 1000 1000 1000 Max break curent KA effective value KA 500 85 50 40 30 17 Overvoltage multiple Do not exceed voltage of 2.5 times of rating Resistance of the fuse pipe (Ω) 93±7 200±10 315土14 Weight Kg 5.6 12.2 15.6 Fuse weight Kg 0.9 1.6 2.5 Overall and mounting dimensions(mm)
FZSW Polymer Insulators
Technical data Type Ratde current (kv) Ratde machincal load(kN) Height (mm) Insulating Li(mm) FZSW-12/4 12 4 215±10 175 FZS-35/6 35 6 445±10 378 FZSW-35/6 35 6 450±10 360 FZSW-66/8 66 8 770±10 670 FZSW-110/10 110 10 1220±10 1085 Type Min. creepage distance (mm) Diameter of shed D.(mm) Full wave lighting requency wet withsand vltage (peak)KV 1min Power requency wet withstand voltage (peak value)KV FZSW-12/4 305 105/80 75 42 FZS-35/6 890 135...
ZN63(VS1)-12 Indoor Vacuum Circuit Breaker (Ins...
Selection ZN63 - 12 T 630 - 25 HT P210 Model Rated voltage(KV) Operating mechanism Rated current(A) Rated short-circuit breaking current(KA) Installation Phase spacing Indoor vacuum circuit breaker 12:12KV T: Spring type 630,1250, 1600,2000, 2500, 3150, 4000 20, 25, 31.5, 40 HT: Handcart FT: Fixed type P150, P210, P275 Note: ZN63-12 adopts a double spring integrated mechanism by default. If a single spring modular mechanism is required, a single spring needs to be added to the mod...